EC25TC Three Phase Active Reactive CT Operated Electricity Meter

Three Phase Electricity Meter with Active-ReactivePower Measurement for High Consuming Costumers

Compact and Lightweight Design
EC25TC Three Phase Active Reactive CT Operated Electricity Meter

Technicial Specifications

Parameters

Voltage

3x230 / 400 V

Meter Constant

10000 imp / kWh, 10000 imp / kVArh

Starting Current, Ist

10 mA

Minimum Current, Imin

50 mA

Nominal Akım, In

5A

Maximum Current, Imax

10 A

Weight

1.0 kg

Model A B C D
EC25TC13CHB 160 230 73 51
EC25TC Aktif/Reaktif X/5 Elektrik Sayacı Kroki EC25TC Aktif/Reaktif X/5 Elektrik Sayacı Kroki

Features

  • MID Certified
  • IEC 50470-1/3 compliance with standards
  • Class B (+1%) active energy metering accuracy
  • UV-protected, Polycarbonate IP54 body
  • Wide Working Range 40V - 320V Maksimum Maximum 100A for EC1 maximum 80A for EC0 Outdoor, -40C... +70C
  • 4 tariffs, 8 time zones, 3 day type, TOU
  • Demand Reset Button
  • 0.5 sec/day real time clock accuracy
  • Automatic Daylight Saving Application (DST)
  • Index reading from display during absence for power
  • Data reading from optical port during absence of power
  • Compliance with TEDAŞ/EPDK Conditions
  • Custom LCD design
  • Ergonomic and lightweight design
  • 10 Years of battery life

Event Logs

  • 10 records for R,S,T Phase power down
  • 10 records for electricity power down
  • 10 records for R,S,T current reverse connection
  • 10 records for phase sequence errors
  • 12 records for terminal cover open and quantity
  • Top cover open

System Solutions

  • Optical Port (IEC62056-21)
  • RS485 port (IEC62056-21)
  • Optional isolated pulse output
  • Optional MODBUS support
  • Optional DLMS/COSEM support

LCD Warning Icons

Elektromed Foreks Elektronik Elektrik Sayaçları Shows that all phases are active
If any fof the phases power down, related phase icon disappears.
In any two of the phases are reverse connected it shows the reverse connected phase symbols
Elektromed Elektronik Elektrik Sayaçları While meter measures active consumption in correct direction, quadrant is shown with correct Elektromed Elektronik Elektrik Sayaçları arrow direction.
Elektromed Elektronik Elektrik Sayaçları If the current is reverse connected, quadrant flashes theElektromed Elektronik Elektrik Sayaçları arrow direction and instead of tariff OBIS codes, related phase symbols Elektromed Elektronik Elektrik Sayaçları flash with Elektromed Elektronik Elektrik Sayaçları (Reverse) symbols.
Elektromed Elektronik Elektrik Sayaçları If the real time clock is in error mode Elektromed Elektronik Elektrik Sayaçları symbol flashes instead of tariff obis codes.
Elektromed Elektronik Elektrik Sayaçları Top cover opening warning
Elektromed Elektronik Elektrik Sayaçları Terminal cover opening warning

Load Profile

  • 15, 30, 60 min adjustable periods
  • 3 channels active, Inductive and capacitive reactive energy
  • Total of 5832 records till 8 months

Protection Features

  • Terminal cover open warning and record
  • Top cover open warning notification and record
  • Independent sealing for terminal and top cover
  • Demand reset button
  • Password protection for programming mod
  • Absolute energy value recording when reverse connected
  • External memory data write protection
  • Previous months values
  • Last 24 months tariff consumption recording
  • Phase sequence error notification and register
  • Reverse current connection notification and register
Elektromed Elektronik Elektrik Sayaçları

Obis Kod

Discription

0.0.0

Serial Number

0.9.1

Meter Clock

0.9.2

Meter Date

0.9.5

Day of the Week

1.8.0

Cumulative Active Energy (import)

1.8.1

Total Energy T1

1.8.2

Total Energy T2

1.8.3

Total Energy T3

1.8.4

Total Energy T4

1.6.0

Maximum Active Power

1.6.0*1

Previous Month Max. Active Power

Obis Kod

Discription

96.71

Last Terminal Cover Open Date

96.70

Top Cover Opening Date

1.8.1*1

T1 Monthly Starting Consumption Value

1.8.2*1

T2 Monthly Starting Consumption Value

1.8.3*1

T3 Monthly Starting Consumption Value

1.8.4*1

T4 Monthly Starting Consumption Value

5.8.0

Reactive Inductive Energy Consumption

8.8.0

Reactive Capacitive Energy Consumption

5.8.0*1

Reactive Inductive Month Starting value

8.8.0*1

Reactive Capacitive Month Starting Dates

0.1.0

Demand Reset Count

0.1.2*1

Last Demant Reset Date and Time

Technicial Specifications

Parameters

Connection type

3 phase 4 wire

Terminal Connection

DIN

Accuracy Class - aktif

Class B or C

Accuracy Class - reaktif

Class 2

Frequency

50 Hz

Protection Class

IP54

Electromagnetic Environment Class

E2

Mechanical Environment Class

M2

Temperature Range

-40...+70 ̊C

Current Circuit Power Consumption

< 2W, 10VA

Voltage Circuit Power Consumption

< 4VA

Display

LCD 9 digit + symbols

Demand Time Range

15 (default), 30 or 60 min

Load Profile

Cumulative Consumption Values (1.8.0, 5.8.0 ve 8.8.0)

Load Profile Periyodu

30 (default), 15 or 60 min

Optical Port

Mode C Readout, 9600baud (IEC62056-21)

Pulse Output

1pulse / Wh

RS485 Port

2500 V insulation voltage, Mode C Readout, 9600baud (IEC62056-21)

Accurate Metering

Our meters have electronic metering(solid state) structure which enables long term high metering accuracy service life. Self consumption is below standart values and all the components are chosen and tested carefully. Reference and basic current values are chosen as 5 A to increase the accuracy.

Our meters perform very accurately on direct connected mode from starting current 100 A, current transformer connected mode up ot 10 A because dynamic range of metering circuits are wide. Even the current ends are connected reversely metering accuracy is in the same values and consumption is recorded as absolute value.

Easy Installation and Stylish Industrial Design

Our electricity meters have small and esthetic design which can easily be installed instead of mechanical meters uninstalled from site. Industrial design is performed by taking long term high performance usage, easy installation and usage and future-proof properties into consideration.

Environmental Friendly

All the precautions for protecting and improving the environment are taken and been applied. From battery decision to package design, at all stages this precision is applied. Our company proved this structure by ISO 140001 Environment Management System certificate.

Special Design Display

Meter display is specially designed large for easy reading. Display messages are supported by symbols for better understanding. Display backlight is standard for combi meters and optional for domestic type meters.

Elektromed Elektronik Elektrik Sayaçları

Remote Reading

In the near future all meters will be read remotely. For remote reading, meters should be equiped with communication module. Most common and economical of these module is RS485. For this reason, Combi meters used by high consuming customers have RS485 output as a standart feature. For domestic mono phase and three phase meter RS485 module is optional.

Ntechnic

We are ready to be your partner with our innovative, sustainable, effective management mentality. We are developing strong and sustained partnerships by offering neoteric solutions.

Contact Us
  • Çamlık Mahallesi, Tütün Sk. No:2-4, 34774 Ümraniye, İstanbul / Turkiye
  • +90 216 325 66 99
  • info@ntechnic.com.tr